Sep 7, 2026 · 11 min · 9 segments
In this episode of EC&M Code Conversations, Editor-in-Chief Ellen Parson and Code Consultant Russ LeBlanc discuss 2026 NEC changes related to a new requirement regarding power control systems (PCS)…
Ellen ParsonHostSo eventually, it will be overloaded if we simply keep adding more and more load.
So eventually, it will be overloaded if we simply keep adding more and more load.
11 min more in this episode
Up next · 7:13
Explains that a PCS monitoring only controlled loads can substitute its control setting for those loads. Uses a 100-amp panel with twelve 20-amp loads as an example. Shows how an 80-amp PCS setting can replace a calculated 240 amps of connected load. Explains calculations when a PCS monitors both controlled and non-controlled loads. Demonstrates how a controlled load may be counted at its minimum operating current, including zero amps.
Search every transcript — find any word, phrase or idea across every show Radar covers
Trends — see what podcasts are suddenly talking about
Alerts — get an email when a brand or person you follow is mentioned
Reports — turn mentions into a PDF report you can share