Russ LeBlanc

Electrical Code consultant and trainer ("The Code Guy"), owner of LeBlanc Consulting Services and NEC columnist for EC&M Magazine.

Nov 2, 2026

2:11
If you could go over what the new requirement is, what does Section 555.35 introduce for GFPE protection systems? And what do you think the intent is behind this particular change?
2:25
Well, there were actually several changes in 555.35. One is the addition of the word peers to cover installations that might not quite meet the definition of docking facilities.
2:38
And 555.35a was revised to require feeders and branch circuits to be protected by listed facilities.
2:46
GFPE rated not more than 100 milliamps.
2:51
And that particular revision brings back the language that was inadvertently omitted for 2023.
2:58
The 2023 required GFPE protection rated 30 milliamps for shore power receptacles and GSI protection for other receptacles installed on branch circuits, but did not require GFPE protection for the entire branch circuit.
3:16
555.35b was added to address ground fault monitoring of fire pumps, and 555.35f was also added to require performance testing of the GFPE systems.
8:06
What might that process involve and what is the electricians, you know, ultimately trying to verify here? And is that a change from the previous code or is that new with this code or was it always like that?
6:00
So what does that listing tell the electrician, for example, about how that receptacle has been designed and tested? So.
6:08
Well, that's a great question.
6:10
And honestly, I don't quite know how to answer that because unless the product safety standard for receptacles has somehow changed overnight, the product standard for receptacles, which is UL489, does not have any specific information about such a listing.
6:28
Perhaps the correct terminology to use here would have been identified for EVSE and WPTE use rather than listed for EVSE and WPTE use.
6:43
Identified means recognizable as suitable for the use, but does not necessarily mean it has been tested by a testing lab.
6:52
like UL or ETL, for example, I know that there are several manufacturers that produce receptacles that are specifically designed or identified for EVSE and WPTE use, but not listed for that use.
8:05
Any advice on, you know, just for our listeners in general, what should contractors, electricians know about existing installations they might be working on where a standard grade receptacle is already being used for EV charging? And then, you know, are there any warning signs of overheating or connection problems they should be looking out for?
8:24
Well, if they are concerned, they should inspect the receptacle and the attachment plug regularly.
5:00
Could you go into a practical example, maybe, of how the listeners would encounter this type of situation in the field?
5:09
Sure.
5:11
So for this example, we're going to use an all-electric house, including electric heat, an electric dryer, an electric range, and all electric appliances.
5:22
The service for the house is rated 200 amps, and the customer wants to add an EV charger.
5:28
But that EV charger could potentially cause that 200-amp service to be overloaded.
5:33
So instead of upgrading to a larger service, the electrician could install one of these power control systems to control the loads and prevent that service from drawing more than 160 amps.
5:46
That's that 80% limit of 200 amp service, right? And so with the PCS installed, for example, the EV charging equipment would only be energized when the total load on the service would not exceed 160 amps.
7:13
So when the code specifically references using these PCS in load calculations, does it change or affect the way electricians and engineers would approach, you know, sizing demand and demand calculations? And if so, how?