Skip to main content
Massimo Pellizzari

Massimo Pellizzari

Massimo Pellizzari is a CO2 specialist and Senior Commissioning Engineer at Daikin group (Daikin Europe), a guest on The Refrigeration Mentor Podcast.

Aug 13, 2026

35:06
When you do enough of them and you work on enough of them, it'll just become second nature.
35:10
In terms of electrical components, we got, uh, three s- electrical switch boxes, one for each section.
35:18
And each switch box has got a front plate and a back plate.
35:22
A back plate because on the back plate we have the inverters' PCB, because they, the inverter PCBs, they have a heat sink, an aluminum heat sink, so they are in the airflow to cool down the, the, the inverter itself.
35:37
And there are also temperature probes on the fins measuring the temperature of the inverter and passing an alarm in case the inverter is overheating.
35:48
Okay.
35:48
Here, so on this, on the back plate of this, uh, the inverter for compressor one.

7 MINS LATER

43:17
Perfect.
11:42
I love it.
11:44
Talking about temperature.
11:45
Yeah.
11:47
temperature you know on transcritical system this chart temperature can be very high it can reach easily 230 Fahrenheit yes but especially in when you are running very high transcritical pressure while Daikin has chosen to do a double stage technology system to reduce the compression ratio and to have a lower discharge temperature.
12:17
So compressor is running in a more reliable way.
12:21
So here on the discharge, we can reach about 160, 150 degrees, not very much.
12:29
So, you know, we got a compressor running perfectly and very much in a reliable situation.

31 MINS LATER

43:49
That makes sense.

We value your privacy