what are they chilling that right down to or is it just like room temperature and that's enough to cool it what what is so we have the
11:43
One of the nodes we have running today is in a 20-year-old data center.
11:49
We're supplying 64-degree air on the cold aisle.
11:58
The AI servers are grabbing that air.
12:01
pushing it out the back north of 100 degrees into a rear door heat exchanger.
12:05
And that rear door heat exchanger is grabbing it basically at the source and spitting out 68 degree hair.
12:11
So you're going from 64 to 68.